The R13192 delivers enhanced sensitivity through a new design of the photosensitive area.
Features
Detects fire from long distances (high sensitivity)
Detects only UV light without using any optical filters
Applications
Fire detection in a building with large space
Arson surveillance
Discharge detection
Specifications
Spectral Response (Short) : 185 nm
Spectral Response (Long) : 260 nm
Electrode Material : Ni
Weight : 5.2 g
[Maximum Rating] Supply Voltage (DC) : 420 V
[Maximum Rating] Average Discharge Current : 3 mA
[Maximum Rating] Peak Current : 50 mA
[Maximum Rating] Operation Ambient Temperature : -40 to +125 ℃
Discharge Starting Voltage (DC) : 260 V
Discharge Sustaining Voltage (DC) : 185 V
Sensitivitiy Typ. : 15000 min-1
Background Max. : 5 min-1
Average Life : 25000 h
[Recommended Operating Parameters] Supply Voltage (DC) : 325±25 V
[Recommended Operating Parameters] Average Discharge Current : 0.3 mA
[Recommended Operating Parameters] Quenching Time Min. : 2 ms
Suitable Socket (Sold Separately) : E678-9C