halogen-free installation cable
enhanced characteristics during fire conditions
Permissible operating temperature of the conductor - +70°C
Short circuit temperature at the conductor - +250°C
Test voltage core/core - 2000 V
Minimum bending radius - fixed 4x Outer-Ø
Copper conductor bare, 1.5 - 10 mm²: solid acc. to DIN VDE 0295 Class 1 / IEC 60228 Class 1;16 - 35 mm²: stranded acc. to DIN VDE 0295 Class 2 / IEC 60228 Class 2
Core insulation: XLPE
Core identification acc. to DIN VDE 0293-308,
1 core(s): black oder green-yellow
2 - 5 core(s): colour coded
7 core(s): black cores with consecutive labeling in white digits
G = with protective conductor GN-YE,
x = without protective conductor
Cores stranded in layers with optimal lay lengths
Core sheating (filling compound) for multi-core cables
Outer sheath: halogen-free polymer acc. to DIN VDE 0207-24 (compound type HM2)
Sheath colour: grey (RAL 7035)
resistant to: ozone
halogen-free
flame-retardant
reduced fire propagation, low smoke development
halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
corrosiveness of combustion gases acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
bundle fire test acc. to DIN VDE 0482-332-3-24 / DIN EN 60332-3-24 / IEC 60332-3-24
smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
ozone-resistant acc. to DIN VDE 0473-396 / DIN EN 50396
certifications and approvals:
EAC