Power distribution cables acc. to DIN VDE 0276-603 / HD 603 S1 / IEC 60502
7 core and above acc. to DIN VDE 0276-627 / HD 627 S1 / IEC 60502
Permissible conductor operating temperature - +70°C
Permissible short circuit temperature (short circuit duration max. 5 s) - 300 mm² +140°C
Test voltage - 4000 V
Highest permissible voltage - Direct current systems: Conductor/conductor 1.8 kV
Direct current systems: Conductor/earth 0.9 kV
Alternating current systems: Single phase systems both outer conductors insulated 1.4 kV
Alternating current systems: Single phase systems one outer conductor earthed 0.7 kV
Three phase systems 1.2 kV
Minimum bending radius - single core 15x Outer-Ø
multi core 12x Outer-Ø
Bare copper conductor,
single wire acc. to DIN VDE 0295 cl.1 / IEC 60228 cl.1
multi wire acc. to DIN VDE 0295 cl.2 / IEC 60228 cl.2
Core insulation: PVC, compound type DIV4 acc. to HD 603 S1
Core identification acc. to DIN VDE 0293-308 / 0276-603
Core colour for 3+½ conductor
J-version: GN-YE (½), BN, BK, GY
O-version: BU (½), BN, BK, GY
Cores stranded in concentric layers
Outer sheath: PVC, compound type DMV5 acc. to HD 603 S1
Sheath colour: black
the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Flame retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
Power cables for energy supply are installed in open air, in underground, in water, in concrete, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not to be expected.