- 2 separate independently adjustable set points
- LED indicators for power supply, contact and reaction timer
Control relay for monitoring DC current and DC voltage with two independently adjustable relay outputs.
Under or over current function can be set independently for R1 and R2 by DIP-Switch selection.
The setpoint (Hyst) can be independently adjusted for both R1 and R2 from 5-50%. At the end of tr, the output relay changes as soon as the measured value exceeds one of the set points (Hyst). The time tr is valid for both relays.
When the measured value returns to within the permitted range, the corresponding relay resets immediately.
Switch “l/Umin” can be used to enable or disable the minimum level control (<4mA or <2V). This could be particularly useful with 4-20mA signals in “Over” function.
supply voltage variation - nominal voltage -15%...+10%
frequency range - 48 - 63 Hz
duty cycle - 100%