The digital output module is required for switching valves, reflux separators, heaters, contactors etc. directly via the DC-Manager™.
The pulse-width modulated output allows quasi-continuous direct control of heaters, motorized control valves, etc.. Thus, there is no necessity for expensive additional control electronics.
The pulse area modulation is an extended form of pulse frequency modulation (XPFM) which minimises the pulse amount and consequently prevents damage to the actuator (e.g. a solenoid or reflux separator).
• 4 active digital outputs
• For direct connection of proportional solenoids
• LED control display
• Short-circuit-proof
• Signal : 4 active digital outputs 1 mHz…1kHz, 2 A per channel, sum load max. 3 A
• Connection type : Plug-in connectors with push-in spring connection or optionally pluggable screw terminals.
• Switching frequency of the outputs : 1 mHz…1 kHz (as frequency, PWM or PFM output)
• Operating voltage : 24 V (18…30 V), supply via bus
• Power consumption : 35 mA (without activation energy)
• Dimensions (HxWxD) : 99.5 x 22.5 x 114.5 mm
• Working temperature : 0…+60 °C
• Storage temperature : 0…+65 °C
• Humidity : 90 %, not condensing
• For the control of : Proportional solenoid valves, solenoid valves, etc.