Use with V5055 or V5097 Gas Valves to control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied; valve opens all the way on demand.
Features & Benefits:
Provide final safety shutoff service when used with V5055 or V5097 gas valve
One-second maximum closing time
Continuously displays the valve position with a red indicator when open and a yellow indicator when closed
Mount in any position directly to valve bonnet with three setscrews
Provide final safety shutoff service when used with V5055 or V5097 Gas Valves
Frequency: 60 Hz Maximum
Safe Operating Pressure (psi): 5 psi
Used With: V5034; V5055; V5097
Approvals, CSA: When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada
Approvals, Underwriters Laboratories Inc.: When used with V5055A-E (3/4 to 4 in.) or V5097A-C (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZ
Approvals, Swiss RE: When used with V5055 or V5097: Acceptable