Features
• - Measuring range : 0-200 or 0-2000ppm
• - Wireless setting by radio, no activation needed on the device
• - Outputs : 4-20mA and/or Modbus RS485
• - Memory : up to 500 000 measures
• - H2S gaz cell changeable on-site
• - Logger enclosure rating IP68
This logger integrates the H2S sensor and some outputs so-called process like 4-20mA and Modbus RS485.
The measurement is performed by an electrochemical cell, the measuring head is easily interchangeable on-site and embarks its calibration.
The sensor has radio communication capabilities up to 100m for configuration and a logger that allows measurement history retrieval also by radio.
Gaz cell features
You have the choice between two types of gaz cell : H2S 0-200ppm (Maximum overexposure 500ppm) or H2S 0-2000ppm (Maximum overexposure 10 000ppm).
They are changeable very easily on-site with the their keyed connector.
Power supply - External : 7 … 30Vdc ; 1Watt max so 150mA (7V) to 40mA (30V)
Internal : lithium battery 3,6V 17Ah (PN : A0100009) used for the autonomous datalogger mode
Process output
External power supply
necessary (8…30Vdc) - – 4-20 mA current loop (the sensor can not be powered by the loop: 3-wires connection required)
– Modbus RS485
Mode ASCII or RTU
Speed (Baud) 600, 1200, … ,19200, 38400, 57600 (default 9600 baud)
8 bits data, 1 stop bit, no parity by default
Configurable slave address (default address =1)
Reading of concentration on the extended Modbus table (@184 cf : K0K00011, available in the configuration of the logger using our software Avelour)