ITR831-001 KNX-DMX Gateway module supports two-way control,
and can record, play and delete DMX programs. With recording
time up to 4 hours, KNX-DMX Gateway can be widely used to control
devices with built-in DMX protocol port for LED color control,
such as computer light, moving head light, laser light, etc.
LAYOUTS AND WIRING DIAGRAM
• Installation: Mount the device on a DIN rail of Distribution box.
• Programming: This device is designed for professional KNX installation.
It can only be programmed by ETS software.
• Don’t connect KNX DC power to other load channels before KNX Bus
installation and wiring.
• Auxiliary power supply: An additional DC 24V power supply should
be connected for DMX interface of the module.
• Do not get AC 240V voltage into Bus wire, it will damage all of devices
in system.
IMPORTANT NOTES
• 3 working modes: DMX recorder mode, DMX dimming mode
( EIB to DMX) and DMX to EIB conversion mode (1bit, 1byte data
point)
• Supported communication signal: DMX512-1990, ArtNet DMX
• Store and playback up to 24 programs, maximum recording time:
4 hours
• DMX recorder mode supports switching and dimming up to 48
channels, which means controlling DMX device via KNX system.
• DMX to EIB conversion mode supports switching and absolute
dimming via DMX signal for up to 48 channels, which means controlling
KNX system via DMX storage control function.
• DMX output signal can be used to control devices with built-in
DMX protocol port for LED color control, such as computer light,
moving head light, laser light, etc.
• DMX input control functions for KNX system include:Sequence
control, Scene control, Switch control, Relative dimming, Absolute
dimming.