Certifications - CEI 61439-1, CEI 61439-2, CEI0-21/A70 (network connection LV);
CEI0-16/A70 (network connection MV)
Voltage - 230/400V – 277/480V – 440V
Frequency - 50/60 Hz
Automation - PLC
Level meter/pressure - includeed, type of analogue signal 4-20 mA
Interface operator panel - color HMI touch screen 10”
Network analyzer - digital, three-phase, measurement of voltages, currents, frequency, cos.f, active/reactive/apparent power
Protections included - network voltage / frequency control protection, generator magnetothermal protection
ANSI code - 27, 57, 47, 78, 81L, 81H, 81R
Shunt power - includeed, through internal capacitor battery or external automatic control board of power factor correction
Protection grade - IP54
OPTIONALS
REMOTE CONTROL AND REMOTE MANAGEMENT WITH REMOTE HMI DUPLICATION BY PC, TABLET OR SMARTPHONE
REMOTE CONTROL AND REMOTE MANAGEMENT BY SMS
REMOTE BOARD CONNECTED TO THE LOADING TANK BY ETHERNET NETWORK OR OPTICAL FIBER
ANTI-CONDENSATION, THERMOSTATED, VENTILATED HEATERS
CABINET WITH GLASS DOOR