• 4 A current output
• Complete with “Daily ventilation” function
• One SHE group (RG) and two ventilation groups (LG)
• PC service port interface for advanced configuration options
• Integrated service timer
• Integrated 24 V DC power supply, emergency batteries and charging pack, parallel operation, 72 hours operational readiness during power cuts
• Monitoring of detector circuits (automatic detectors and SHE manual call points), emergency batteries and connected drives
• Optional cascading of up to 8 control panels
• DIP switch for adjustable special functions
• TÜV type tested
• Tested to EN 12101-10
Cennection facilities
• 24 V DC drives with separate cutoff (load interruption, limit switch)
• total power consumption of all connected drives max. 4 A or 8 A depending on type of control panel
• 10 SHEV control points RBH/3A... (line terminal via attached terminal resistor)
• 10 automatic detectors in 2-conductor technology, optical smoke detectors and/or heat differential detectors and/or
• 10 automatic detectors in 2-conductor technology, optical smoke detectors and/or heat differential detectors and/or maximum heat detectors (line terminal with active end module or terminal resistor) factory-fitted via attached terminal resistor
• 10 external ventilation switches OPEN/STOP/CLOSE (e.g.: type LTA 25) per ventilation group, max. two ventilation groups
• Power supply 24 V DC - 100 mA for one wind/rain detector WRS 24V or one rain detector RS
• one connection each for potential-free signal of SHEV triggered and malfunction plus transmission of wind/rain signal; contact load 30 V / max. 2A
• Maximal 8 control panel Slave are cascadable