Benefits/Features:
4 A current output
Complete with “Daily ventilation” function
One SHE group (RG) and two ventilation groups (LG)
PC service port interface for advanced configuration options
Integrated service timer
Integrated 24 V DC power supply, emergency batteries and charging pack, parallel operation, 72 hours operational readiness during power cuts
Monitoring of detector circuits (automatic detectors and SHE manual call points), emergency batteries and connected drives
Optional cascading of up to 8 control panels
DIP switch for adjustable special functions
TÜV type tested
Tested to EN 12101-10
Technical data:
Electrical properties
Primary power supply
Mains supply voltage: 230 V AC/50 Hz, (±10 %), separately fused
System voltage: 27 V DC (nominal) (-25 % /+10 %)
Power consumption: approx. 150 W at 4 A current output
Power consumption (standby): < 5 W
Connection terminal Screw terminal: max. 2.5 mm²
Fuse: Mains: 230 V AC; T 3.15 A/H, motor circuit FKS 10 A
Secondary power supply
Rechargeable battery 2.2 Ah
Current output after 72 h in emergency power operation 4 A for 180 sec.(according to DIN EN 12101-10)
Output: Voltage 27 V DC (nominal), (-25 % /+10 %) smoothed
Power Pmax = 108 W, Pmin = 0 W
Current (nominal): Actuators: 4 A at ED 30, output separately fused,Holding solenoids: 1 A at ED 100 at ED 100
Opening/closing: Reversal of voltage polarity
Automatic release OPEN/CLOSED direction: after 3 min. (in ventilation mode)
Line monitoring: via diodes
Connection terminal: max. 6 mm², screw terminal
Fuse: FKS 10 A