Robust digital pH sensor for operation on TriBox controllers and HS100 DIN G2 rail module. Digital communication ensures safe and trouble-free signal transmission from the sensor to the controller. The high-quality gel pH electrode has a hole diaphragm and is insensitive to dirt, making the sensor ideal for wastewater applications.
High-quality combination electrode with hole diaphragm and polymerised solid electrolyte
Low maintenance
Plug and play with TriBox controller
Measurement technology - pH-electrode
Measurement principle - Potentiometry
Parameter - pH value, temperature
Measuring range pH - 0...14 pH
Resolution - 0,01 pH
Intrinsic error - pH1 - ± 0.05 pH
pH7 - ± 0.05 pH
pH13 - ± 0.35 pH
Linearity measurement error - ± 0.1 pH
Repeatability - pH1 - ± 0.1 pH
pH7 - ± 0.05 pH
pH13 - ± 0.1 pH
Output signal fluctuation - pH7 - ± 0.025 pH
- pH4 - ± 0.05 pH
Warm-up time - < 5 min
Drift - Short-term drift 24 h - ≤ 0.03 pH
Long-term drift 1 week - ≤ 0.05 pH
10% time and90% time - T10 ascending - < 2 s
T10 falling - < 2 s
T90 ascending - ≤ 5 s
T90 falling - ≤ 5 s
Temperature compensation - Pt1000
Measurement interval - 2 s
Housing material - PPS / PET / NBR