The pump shall be designed for clean and clear room temperature water to be used in fire fighting application.
The pump casing shall be of Cast Iron grade FG 260 as per IS 210 / ISO 186 with inline suction and discharge port.
The pump casing shall have threaded ports near suction and delivery flanges for installing suction and discharge pressure gauges. The pump shall also have a threaded drain port at the bottom of casing for draining the pump during maintenance.
The pumps shall have closed type impeller with Bronze LTB2 (standard supply) & Cast Iron FG 260 material.
The diesel engine shall be supplied with Radiator cooled type(standard supply) or Heat exchanger type.
The diesel engine shall be supplied with 12 volts DC or 24 volts DC battery and connection cables.
The pump accessories Suction and discharge pressure gauge & Casing relief valve shall be supplied on request.
The entire pump set including base plate and diesel engine are to be painted with RAL3002 shade.