The MPNC020 module has digital inputs/outputs and it can be used as extension of PLC (TPAC) / operator panels (TP) and any other panel that has a Modbus RTU or CANopen communication protocol.
Depending on the communication interface it is necessary to add a "head" to communicate with panel: MPNC010 for CANopen protocol and MPNC006 for Modbus protocol.
Up to 16 analog and digital modules can be added in the same line.
The MPNC020 is available with:
16 Digital inputs (PNP 0-24Vdc)
16 Digital outputs (PNP 0-24Vdc). See ACIN01 product for relay outputs.
Features
Digital inputs: (PNP 0-24Vdc)
Digital otputs: (PNP 0-24Vdc)
Max current for every output: 500mA
Max current for all outputs: 2A
Power supply: 24Vdc ±15%, 3W
Dimensions: 115(l)x115(h)x(22.5mm depht)
Working temperature: 0-50°C
Protection: IP20