Insulation tester Isolab series
surge protection device

insulation tester
insulation tester
Add to favorites
Compare this product
 

Characteristics

Test type
insulation
Tested product
surge protection device

Description

To test the insulation resistance to DIN VDE 0100 Part 610 and the characteristic curve behaviour of the following surge voltage and lightning current arrestors: V10-C and V20-C: Uc Tolerance range 75 V -> 110 V - 130 V 150 V -> 215 V - 265 V 280 V -> 385 V - 475 V 320 V -> 460 V - 560 V 335 V -> 460 V - 560 V 385 V -> 560 V - 680 V 440 V -> 645 V - 785 V 550 V -> 820 V - 1,000 V V25-B+C and V50-B+C: Uc Tolerance range 150 V -> 215 V - 265 V 280 V -> 385 V - 475 V 320 V -> 460 V - 560 V 385 V -> 560 V - 680 V Varistor arrestors of other manufacturers can be tested for 1 or 3 mA characteristic curve behaviour Battery operation Measuring cables contained in the scope of delivery.

Catalogs

No catalogs are available for this product.

See all of OBO Bettermann‘s catalogs
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.