• Developed for early warning in clean rooms with high demands to quick detection of smoke and fire gases.
• Lazeer indicates presence of smoke in three preset levels, and can be configured to raise the alarm at any one of these levels.
• Two pipelines - one detection zone.
• 2x100 meter pipe length.
• Self calibrating without any need at all for manual adjustments.
• Tested and approved according to EN54-4 and EN54-20, class A and B
• VdS approval: G 211092
• CPD: 0786-CPD-21084
• Voltage: 230 V AC
• Operating temperature: - 30 to +55 °C
• WiFi
• Ambient humidity: < 98%
• Dimensions: 272 x 530 x 143 mm
• Weight: ~6600 g
• IP44