PSSu, electronic module, failsafe, counter, 2 operating modes, configurable, 1 input, incremental encoder, differential signal RS422, resolution 32 Bit, for increased environmental requirements.
General data
Approval - CE
UKCA
cULus Listed
TÜV
EAC (Eurasian)
Application range - Fail-safe
Technical data
Input incremental encoder
Type of inputs incr. enc. - Inkrementalgeber
Signal input A, B and/or C - Differenzsignal (RS-422)
Evaluation counter puls incr. - 1-fach
Pot. isol. incr./per. supply - ja
Pot. isol. incr./mod.supply - ja
Environmental data
Climatic suitability to ... - EN 60068-2-30
EN 60068-2-2
EN 60068-2-1
EN 60068-2-78
EN 60068-2-14
Ambient temperature standard - EN 60068-2-14
Ambient temperature - -40
Storage temperature standard - EN 60068-2-1/-2
Climatic suitability standard - EN 60068-2-30
EN 60068-2-78
Humidity rating - 93 % r. F. bei 40 °C
Condensation permitted? - kurzzeitig
Perm. operating height ASL - 5000 m
EMC to standard ... - EN 61000-6-2
EN 61000-4-4
EN 61000-4-5
EN 61000-6-4
EN 61000-4-6
EN 61000-4-2
EN 61000-4-3
Vibration to standard ... - EN 60068-2-6
Broad band noise to - EN 60068-2-64
Acc. shock to standard1 - 15g
Acc. shock to standard2 - 25g
Clearance & creepage dist. to - EN 60664-1
Overvoltage category - II
Pollution degree clear.&creep. - 2
Protection type standard - EN 60529
Protection type, mounting - IP54
Protection type, housing - IP20
Terminal protection type - IP20