PCT200Ai is the CT/PT test set (current transformer analyzer) that can finish various current transformer test of different CT and plus reference testing functions of PT. Compared with PCT200i, its accuracy is higher. This CT analyzer can test the 0.2s class CT. PCT200Ai- the high-accuracy current transformer testing equipment has passed the tests held by Wuhan High Voltage Research Institute. Within built-in testing software based on Windows system in its local screen, PCT200Ai is the test tool to finalize all the Current transformer testing without laptop control. And the reports can be managed and analyzed on PC and converted to multi-results reports in excel format.
Features
● CT ratio error test accuracy upto 0.02%
● Can test M/P/TP type, bushing and GIS type CT
● Ratio check up to 30000 : 1 and 45000 : 5
● Knee point/Excitation Test check up to 45000V
● One test can get all CT parameters
● PT test functions are also in-built, Polarity, Ratio, Excitation, Burden
● More than 100,000 reports can be saved in its local storage, and support report software used on the kit and on PC for managing and analyzing the reports.
● Built-in Auto-assessment Function: PASS or Fail judgement after testing
● Standards: IEC60044-1/6, IEC61869-2, ANSI/IEEE C57.13, IS2705
● Results saved in Excel format
● Report can be transferred to flash disk via USB port and view and print the report on a PC
● Report could be customizable
● Local Sunlight readable LCD display, 8.4 inch screen, within built-in Windows 7 system
● Weight: 14kg
Following PT tests can be done automatically
● Polarity
● Ratio
● Excitation
● Burden