Interface -
Interface - Profibus DP
Profile - DPV0, DPV1 and DPV2 Class 2 (EN50170 + EN50254)
Diagnostics - Memory
Manual Functions - Address selector switch 0-99 and terminal resistor (with connection cap)
Features - Round Axis
Transmission Rate - ≤12 Mbaud
Interface Cycle Time - ≥ 1 ms
Programming Functions - Resolution, gearing factor (physical resolution) , velocity scaling + filter, preset (zero point), counting direction, limit switches , node number, teach-in, diagnosis
Outputs -
Output Driver - Profibus Data Interface, galvanically isolated via opto-couplers
Electrical Data -
Supply Voltage - 10 – 30 VDC
Power Consumption - ≤ 2.5 W
Start-Up Time - < 1 s
Reverse Polarity Protection - Yes
Short Circuit Protection - Yes
EMC: Emitted Interference - DIN EN 61000-6-4
EMC: Noise Immunity - DIN EN 61000-6-2
MTTF - 109 years @ 40 °C
Sensor -
Technology - Optical
Resolution Singleturn - 13 bit
Accuracy (INL) - ±0.0220° (14 – 16 bit), ±0.0439° (≤13 bit)
Code - Binary
Environmental Specifications -
Protection Class (Shaft) - IP66/IP67
Protection Class (Housing) - IP66/IP67
Humidity - 98% RH, no condensation
Mechanical Data -
Connection Cap Material - Stainless Steel V4A (1.4404; 316 L)
Housing Material - Stainless Steel V4A (1.4404, 316 L)
Housing Coating - No Coating
Flange Material - Stainless steel V4A (1.4404, 316 L)