Eaton's SP2 is a compact surge protective device with a 45KA per phase footprint and one-inch molded nipple that makes this device easy to install on point of use locations, control panels, load centers and small distribution panels (up to 200amp). With a 10KA nominal discharge rating (ln), low VPR ratings and a 200KA SCCR rating, Eaton's SP2 series surge protective device are ideal for type 1 and 2 applications where dependable performance is required.
Made for any environment
A compact UV-resistant NEMA 4x enclosure means this surge protection device can be using in indoor or outdoor applications
Visually access the health of your protection
An LED status indicator provides surge protection status at-a-glance with a green indicator light.
Mounting options for any application
The SP2’s compact footprint, half-inch molded nipple and optional din rail mounting kit make this surge protection device easy to install anywhere you need it.
MARKETS
Light commercial and UL 508A panels
SYSTEM TYPES
Split-phase
INSTALLATION
two-, three-, four-wire
MAXIMUM CONTINUOUS OPERATING AC VOLTAGE
Matched to nominal voltage
PROTECTION
Surges and transients
SCCR
200 kA
NOMINAL DISCHARGE CURRENT
10 kA
MAXIMUM DISCHARGE CURRENT
45 kA
RESPONSE TIME
<25 ns
FREQUENCY
50/60 Hz
OPERATING STATUS/FAULT INDICATION
One bi-color LED
(green: good, red: replace)
CONDUCTOR GAUGE/LENGTH
10 AWG stranded copper/ 18 inches
MOUNTING
Chase nipple/bracket
ENCLOSURE RATING
NEMA 4X
UL 94-5VA
DEGREE OF PROTECTION (INSTALLED STATE)
IP20
(finger-safe)
INSTALLATION LOCATION
Indoor/Outdoor
CIRCUIT LOCATION
Lineside/Loadside
STANDARDS/AGENCY INFORMATION
UL 1449 3rd edition
Type 1 listed SPD
cULus