1 Channel RS 485 PROFIBUS diagnostic repeater module with integrated quality-oscilloscope for 12 Mbps with diagnostic LEDs and redundancy feature. Bus connection is utilized by screw terminals and additional DB9 connector.
The repeater channel and the integrated oscilloscope are directly connected with the ProfiTrace OE core in the 1B/1C Head Station. Scope images and busmonitor data are directly available in the web server.
The advanced 12 Mbps core of the repeater module can be cascaded unlimitedly and has increased RS 485 strength. The data traffic is constantly monitored for glitches which are digitally filtered out. It has on-board switchable termination and able to drive 31 devices.
1 Bus channel
31 devices/bus-loads per channel
1200 m cable length (depends on baudrate)
No limit in cascading
Termination switches for each channel
Removable screw terminals and 1 DB9 connector
Protocol
Transparent for all PROFIBUS protocols
9.6 kbps .. 12 Mbps (auto detection)
2 bits delay time (12 bits in redundant mode)
No address required
Bus redundancy (selectable)
Transmission speed detection: Auto detect (< 10 s detection and 50 s time out)
Delay time (normal mode): 2.0 TBit at 9.6 kbps .. 3 Mbps; 2.75 TBit at 6 Mbps; 3.75 TBit at 12 Mbps
Delay time (redundant mode): 12.0 TBit at 9.6 kbps .. 3 Mbps; 12.75 TBit at 6 Mbps; 13.75 TBit at 12 Mbps
Delay time jitter: Max. ¼ Tbit
Wire diameter (for the screw terminals): < 1.5 mm2
Wire type: stranded or solid core