• Individually Configurable Digital I/O’s for nominal 24 volts signals and 1 amp (2 Amp) loads, Built in input and output functions,
• Individually Configurable Digital I/Os for nominal 24 volts signals and 1 amp (2 Amp) loads.
• Built in input and output functions.
• Autonomous counting to 200 Hz
• Load current measurement
• Input Voltage measurement and scaling
• Overload/Underload protection and Alarming.
• Advanced internal self testing.
• Wide power supply range.
• Wide temperature range.
The PD 620 has four independent digital channels capable of being configured for input or output. Each channel is also capable of measuring a scaled voltage input, and can therefore be used as an analogue input device. It can be used with the BM 014 for direct I/O terminals or the BM 008 base module, where four output channels can be used with the four built in relays.
Power Specifications
Power Supply DC: nom. 24.0 V, min. 18.0 V, max. 32.0 V
Ripple: max. 5%
Power consumption @ 24VDC
All outputs/inputs = ON: max. 45 mA
All outputs/inputs = OFF : max. 30 mA
Current requirement at power up: max. 60 mA
Digital Input
Input voltage at ON: 9 V
Input hysteresis: min. 0.3 V
Input current at ON: max. 3.4 mA
Input frequency: max. 200 Hz
Digital Output
Start current (Duration max 2 sec.): max. 2 A *)
Load current at ON (Sink only): max. 1 A