Refrigerant Infrared Gas Sensor – Dynament Platinum Series
Refrigerant IR Sensors
Features
• Sensors available to cover the LEL range for R32 and R454b
• Plug-and-Play functionality: Each sensor contains all the necessary optics, electronics and firmware to provide a linearized, temperature-compensated output. Expedites the time to market
• USB powered Premier Configuration Unit allows the user to calibrate and re-configure the sensor parameters. PC software includes datalogging feature
• Manual calibration option can be performed without digital commands
• High degree of EMC protection
PST offers a range of refrigerant infrared gas sensors that measure R32 and R454b gases over the LEL range. The sensors are designed with non-dispersive infrared technology and respond to many refrigerant gasses.
The Platinum series platform provides a linearized, high resolution measurement of R32 or R454b over the lower explosive limit range.
Sensor ranges:
• R32 0-15% volume
• R454b 0-12% volume
SPECIFICATION
Operating Voltage Range : 5.0 V d.c. +/- 0.1V
Operating Current : Constant current operation, current range 75 – 85mA
Outputs : Analogue: 0.4-2.0V
Digital: Dynament protocol
Gas measuring range : 0-15% Difluoromethane (R32)
Resolution : 0.1% volume
Linearity : The output is linear within ± 10% of the applied gas, or +/-0.05% volume, whichever is greater.
Accuracy : ± 10% of the reading, 1 bar pressure, 7% volume applied gas at 20°C
Pressure : ± 5% of the calibration pressure to maintain the accuracy limits
Warm up time : To final zero ± 10% full-scale: 5 minutes
Response Time T90 : <30s
Long term zero drift : ±1% full scale per month