Harmonic correction - active
Power factor - 0.95
Input inrush current limitation - active
Input inrush current - 10 A / 4.5 A
External input fuse recommendation - B-10 A / C-10 A
Output data
Power reserves - 20 % Power Boost
Derating - 12 W/°C for >+60 °C
Ripple and noise voltage max. - 50 mVpp
Overview
Dimensions (WxHxD) - 48 mm x 124 mm x 127 mm
Weight per unit (excl. packaging) - 850 g
Operating temp. range - -40 °C to 70 °C
Connection method - Plug connector
Efficiency, typ. - 95.2 %
Power losses, typ. - 24.2 W
MTBF SN 29500 @ 40 °C (h) - 543000 h
DC-OK signal - yes
Width only 48 mm
Built-in decoupling mosfet for 1+1 and n+1 redundancy
Efficiency up to 95.2 %
20 % Output power reserves
Safe HiccupPLUS overload mode
Easy fuse breaking – 3 times nominal current for 12 ms
Minimal inrush current surge
Full power between -40 °C and +60 °C
DC-OK relay contact
Current sharing feature included