DC Input voltage - DC 110 V - 300 V (± 20 %)
Harmonic correction - active
Power factor - 0.96
Input inrush current limitation - active
Input inrush current - 6 A / 9 A
External input fuse recommendation - B-6 A / C-6 A
Output data
Power reserves - 20 % Power Boost
Derating - 4.8 W/°C for >60 °C
Ripple and noise voltage max. - 50 mVpp
Overview
Dimensions (WxHxD) - 39 mm x 124 mm x 117 mm
Weight per unit (excl. packaging) - 600 g
Operating temp. range - -25 °C to 70 °C
Connection method - Screw terminals
Efficiency, typ. - 94.3 %
Power losses, typ. - 11.6 W
MTBF SN 29500 @ 40 °C (h) - 690000 h
DC-OK signal - yes
Width only 39 mm
Efficiency up to 94.3 %
Excellent partial load efficiency
20 % Output power reserves
Safe HiccupPLUS overload mode
Easy fuse breaking due to high overload peak current
Minimal inrush current surge
Full power between -25 °C and +60 °C
Remote ON / OFF function
DC-OK relay contact