Power factor - 0.97
Input inrush current limitation - NTC
Input inrush current - 2.6 A / 6 A
External input fuse recommendation - B-6 A / C-6 A
Output data
Power reserves - 600 W (up to 5s)
Derating - 6 W/°C for +45 to +55 °C
10 W/°C for +55 to +70 °C
20 W/1000 m for altitudes >2000 m
Ripple and noise voltage max. - 50 mVpp
Overview
Dimensions (WxHxD) - 181 mm x 183 mm x 59 mm
Weight per unit (excl. packaging) - 1200 g
Operating temp. range - -25 °C to 70 °C
Connection method - Input: 7/8" 3pin | Output: 7/8" 4pin
Efficiency, typ. - 95.7 %
Power losses, typ. - 13.5 W
MTBF SN 29500 @ 40 °C (h) - 384000 h
DC-OK signal - yes
600 Wpeak 5s
Outputs for actors and sensors separately protected
95.7 % full load and excellent partial load efficiencies
DIN rail mounting possible, option “D”
Output connected to PE (PELV)
Version without connection to PE on request
Large output capacitors
Not potted
Negligible low input inrush current surge
Full power up to +45 °C
IO-Link
Input: 7/8" 3 pin | Output: 2x 7/8” 4 pin