Power factor - 0.97
Input inrush current limitation - active
Input inrush current - 2.6 A / 6 A
External input fuse recommendation - B-6 A / C-6 A
Output data
Power reserves - 600 W (up to 5s)
Derating - 6 W/°C for +45 to +55 °C
10 W/°C for +55 to +70 °C
20 W/1000 m for altitudes >2000 m
Ripple and noise voltage max. - 50 mVpp
Overview
Dimensions (WxHxD) - 181 mm x 183 mm x 59 mm
Weight per unit (excl. packaging) - 1200 g
Operating temp. range - -25 °C to 70 °C
Connection method - Input: 7/8" 3pin | Output: 7/8" 4pin
Efficiency, typ. - 95.7 %
Power losses, typ. - 13.5 W
MTBF SN 29500 @ 40 °C (h) - 384000 h
600 Wpeak 5 s
Outputs for actors and sensors share one channel
95.7 % full load and excellent partial load efficiencies
Output connected to PE (PELV)
Version without connection to PE on request
Large output capacitors
Not potted
Negligible low input inrush current surge
Full power between -25 °C and +55 °C
IO-Link
Input: 7/8" 3pin | Output: 3 x 7/8” 4pin