Power factor - 0.9
Input inrush current limitation - active
Input inrush current - 1.5 A / 1.5 A
External input fuse recommendation - B-6 A / C-6 A
Output data
Power reserves - 600 W (up to 60s)
Derating - 10 W/°C for +55 to +70 °C
Ripple and noise voltage max. - 100 mVpp
Overview
Dimensions (WxHxD) - 182 mm x 272 mm x 70 mm
Weight per unit (excl. packaging) - 1550 g
Operating temp. range - -25 °C to 70 °C
Connection method - Input: HanQ4/2 | Output: QuickON
Efficiency, typ. - 95 %
Power losses, typ. - 15.8 W
MTBF SN 29500 @ 40 °C (h) - 814000 h
DC-OK signal - yes
450 W continuously for 60s
600 Wpeak 1 s
Mounting bracked included
95.2 % full load and excellent partial load efficiencies
Output connected to PE (PELV)
Version without connection to PE on request
Large output capacitors
Not potted
Negligible low input inrush current surge
Full power between -25 °C and +55 °C
DC-OK relay contact
Input HanQ4/2 / Output QuickON