Available as 2 pole OFF switch or changeover switch
Enclosure made of optical fibre reinforced polyester resin
Degree of protection IP66 according to IEC/EN 60529
Clear position indicator 0/1 or ON/OFF
Functional Description - The installation switches series 8040/11-V30 are used for lighting installations. Due to the 90° switching, the switching position is clearly indicated. This is an advantage if the lighting installation and the switch are located in different rooms. The fluorescent rotary actuator allows orientation in case of a lighting failure.
EXPLOSION PROTECTION
Scope of validity - European Union (ATEX), IECEx
Application range (zones) - 1, 2, 21, 22
IECEX gas certificate - IECEx PTB 06.0025
IECEx gas explosion protection - Ex db eb IIC T6 Gb
IECEx dust certificate - IECEx PTB 06.0025
IECEx dust explosion protection - Ex tb IIIC T80 °C Db
ATEX gas certificate - PTB 01 ATEX 1105
ATEX gas explosion protection - II 2 G Ex db eb IIC T6 Gb
ATEX dust certificate - PTB 01 ATEX 1105
ATEX dust explosion protection - II 2 D Ex tb IIIC T80 °C Db
Certificates - ATEX (PTB), Brazil (ULB), China (NEPSI), IECEx (PTB), India (PESO), Taiwan (ITRI)
Ship approval - DNV GL