General
RDW1 Series circuit breaker is mainly used in rated service current up to 6300A of distribution networks to distribute electric energy and protect lines.
● AC rated current: 630-6300A;
● Short-circuit breaking capacity: 80kA-120kA;
● Rated working voltage below AC690V;
● Both the 3 poles and 4 poles are available;
● Two types:Draw-out type and fixed type;
● Equipped with many types of intelligent controllers with different functions;
● Standards: IEC60947-2, GB14048.2.
Operation Conditions
• When the ambient air temperature is -5°C to +40°C. the mean value is no greater than +35°C within 24 hours.
• Altitude: not higher than 2000m for the installation site.
• When the ambient air température is +40°C, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower température; for example, for the wettest month. the maximum relative humidity averaged shall be 90% while the lowest temperature averaged in that month +20°C. and spécial measures shall be taken for the condensation occasionally produced due to température change.
• Pollution grade; Class 3.
• The installation category of the breaker's main circuit is IV and the control circuit and auxiliary circuit being III.
• The circuit breaker should be installed according to the manual.The vertical tilt angle should not exceed 5°.
• If the air circuit breaker is installed in a small compartment of the switch board, the protection grade is up to IP40.
Feature
a. Intelligent controller types; H type (communication type). M type (standard type), L type (économie type). 2M type (high immunity type) and 2H type (high immunity communication type);