Pressure vacuum Valve with ribbon coil is a Protection System:
deflagration end of line flame arrester in according with Directive 2014/34/EU and harmonized
standard EN ISO 16852:2016.
- Stage I vapor recovery compliant.
- The Flame Arrester protects tank from outside fire.
- Surface Protection System is for ail ATEX zone (0,1 and 2).
- Vapor recovery of Truck system shall be connected for fill storage tank. -
Inflammable gases and vapors classification is necessary to correct use of flame arrester.
UE-Type Examination Certifieate EPT 19 ATEX 3333 X is for Explosion Group “IIB3” tested
with Ethylene and compatible for ail gas with MESG 0.65 mm for example:
Ammonia, Industrial methane, Blas-furnace gas, Carbon monoxide, Propane, Butane,
Pentane, Esane, Eptane, Iso-octane, Decane, Benzene, Xilene, Cyclohexane, Acetone,
Ethyl-methyl-ketone, Methyl acetate, Ethyl acetate, Normal propyl acetate, Normal
butyl acetate, Amyl acetate, Cloroethylene, Methanol, Ethanol, Iso Butanol, Normal Butanol,
Amyl aie ohol and Ethyl nitrite. Use only for gas or vapor with MESG 0.65 mm.
Marked “IIC” for Hydrogen and gas/vapor with MESG < 0.5 mm 197 EN-P H2.
Burning rating BC=b and teT=1 min and for “H2” model BOc and tBîz0 min.