ST4602Remote is an additional remote display for DST4602Evolution, allowing remote control and configuration. It can also be connected to DST4602 Standard.
It shares the same dimensions and look & feel of the main controller (same 7" TFT colour display, same lamps and similar push-buttons).
It also allows the same manual operations.
DST4602Remote can be connected to the DST4602Evolution by:
-RS485 insulated serial port (max 800mt):
(only one DST4602Remote is allowed for each DST4602Evolution).
-Ethernet(max. distance 100mt without any hub):
(up to five DST4602Remote is allowed for each DST4602Evolution).
-Remote START/STOP commands for the genset.
-Remote OPEN/CLOSE commands for the circuit breakers.
-Remote acoustic horn muting.
-Remote faults acknowledgment & reset.
-Remote parameters configuration.
-Local/remote communication settings available from the front panel or by BoardPrg3.
Controls
Key selector controls
-Command disabled: no operation is allowed.
-Command enabled: all operations are allowed.
-Remote reset: reset of alarms/warnings.
Push buttons
-REMOTE START: starting is enabled if the operating mode of the local controller is in AUTO.
-REMOTE STOP: used to remotely stop the genset.
-If the genset has been started by the DST4602Remote, the “REMOTE STOP” stops the genset with the cooling operations.
-If the genset has been started by the local DST4602, the “REMOTE STOP” stops the genset immediately without any cooling operations.
-GCB :for manual opening/closure of the Genset Circuit Breaker.
Security
System safety can be increased with a dedicated password