LED-Floodlight/ plane surface floodlight for Ex-Zone 2/22
Series nD8700...
Applications:
Hazardous locations of Zones 2 (gas atmosphere) and 22 (dust atmosphere), indoor and outdoor areas, stockyards, e.g. construction sites, transport routes, pipe bridge, pedestrian areas etc.
Design:
Housing and glass retaining frame are made from diecast aluminium, DB 702N (mica-iron paint). The glass frame is locked by 2 socket head cap screws (M6) and it is hinged to the body after opening. The electrical components are located inside, silicone gasket.
Front cover: Thermal safety glass, impact resistance IK08.
Optic: lens optics with narrow-wide, narrow, or asymmetric light distribution, or without Optics wide beam, Multi-Layer technology.
Connection terminal: 3-pole terminal max. clamping range 2,5mm².
Cable entry: 1 gland M20 x 1.5.
Installation: mounting bracket, swivel range 180°.
Standard Mounting: Facing downwards or horizontal.
Technical Data:
LED: Highpower-LED 4,000K, CRI > 70, life cycle L90 > 100.000h at max. ambient
temperature.
ECG: 220 - 240V, 50-60Hz, Surge voltage resistance 10kV, overload and short circuit
protection.
Note:Due to the inrush current of the electronic ballasts, the maximum permissible
number of light fittings per circuit breaker is limited.
Ambient temperature: -30°C up to +40°C