CLIMATE REGULATOR
Climate regulator for systems with traditional heating and / or floor heating. It allows to manage 3 outputs (3 + 1 Relays) and 4 inputs Probes, 1 input for the thermostat environment and input 1 for the Remote Controller.
Selecting a plant, the climate regulator automatically manages the inputs and outputs used in the plant chosen.
The types of plants are the following:
1) A 3-way valve and the circulation pump is not expected to use the recirculation pump, type of management with PI 3-point adjustment.
2) A 3-way valve and the circulation pump , optional use of the recirculation pump, type of IP management , adjustment to 3 points.
3) Burner flame (stage 1) and the circulation pump, optional use the recirculation pump , type of management ON - OFF , 2-point control.
4) Two-flame burner (2-stage) and the circulation pump, optional use the recirculation pump , type of management ON - OFF , 2-point control.
TECHNICAL FEATURES
Power supply 230V~ ±10% 50/60Hz
Output (relay) 3x2(1)A @ 250V~ SPST - 1x2(1)A @ 250V~ SPDT
Working range -20 .. +120°C
Working curves 0.5 .. 4 T mand./T est.
LCD display Backlit
Type of regulation Comfort/Economy/Antifrost/Off
Sensors (included) 4xNTC (10K Ohm @ 25°C)
Programming Clock Hourly / Weekly
Dimensions H108 W156 D47mm
Protection grade IP40
Class Reg.2013/811/EC VI = 4,0%