• Compatible for 1 phase 2 wire, 3 phase 3 wire, 3 phase 4 wire systems
• Accuracy of ± 0.5% for voltage & current, 0.1% for Frequency, 0.01% for PF, 1% for Power, Class 1 for Active, reactive & Apparent energy
• Max/Min power Demand measurement, Import/Export Energy measurement
• %THD upto 31st level, RS485 Communication MODBUS RTU (MFM376-C-CE)
• CE certified
Brief Specifications
Display Type : 7 Segment LED Display
Display Configuration : 3 Rows of 4 Digits
Electrical Connection : 3Ø - 3W, 3Ø - 4W, 2Ø - 3W, 1Ø - 2W
Type of Output : Pulse Output
Features : Phase Angle Detection, (Max/Min) Demand Power, Run Hour, Auxiliary Interrupts
CT Primary : 1 / 5A to 10kA (Programmable for Any Value)
PT Primary : 100V to 500kV (Programmable for Any Value)
PT Secondary : 100V to 500V (Programmable for Any Value)
Rated Input Current : Nominal 5A AC (Min - 14mA Max - 6A)
Supply Voltage : 240V AC (-15% to +12%) (MFM376-230VAC) ,85V to 270V AC & 40V to 270V DC (MFM376-C-CE)
Size : 96 x 96mm
Mounting Type : Panel Mount