• Monitors: Phase loss, Phase unbalance, Phase sequence, Overload trip current, Under / Over current
• Suitable for 1Ø or 3Ø motors.
• Accuracy: 5% of set value.
• 2 C/O (DPDT) output relay.
• Auto / Remote test available.
Brief Specifications
Measuring Parameter : Overload Current, Phase Asymmetry, Phase Failure & Phase Sequence, Under Current
Electrical Connection : 3Ø-3W
Display : 3 LED Indication
Trip Setting : Phase Unbalance: 50% of Motor Current (Fixed),
T(sec) Setting: 2 , 4, 6 , 8 ,10 Sec Trip Time Curve in Overload Trip Curve Graph,
Under Current: 50% of Motor Current,
X Imax: To Select Motor Current Rating
Time Ranges : Single Phase Trip: 5sec,
Phase Unbalace: 5sec,
Phase Sequence: 5sec,
Overload Trip: As Per (IDMT Curve) ,
Under Current Trip: 5 Sec
Accuracy : Trip: ±5% of Set Value,
Time: ±5% of Setting ±100ms
Output Contact : 2 C/O (DPDT )
Output Rating : NC: 5A @ 240V AC , NO: 5A @ 240V AC
Supply Voltage : 230V AC ±15% ,415V AC (±15%)
Size : 52.5mm
Mounting Type : DIN Rail Mount