S311G is both a digital indicator with analog input (V, mA, Ohm) and voltage/current generator. It is expandable with ModBUS interface which allows the analog retransmission of the measured value to an isolated output in voltage or in current.
S311G has two operanting modes: "AUTO" where it measures an analog value and retransmits it on the output; "MANUAL" where it generates a defined value on the output. In manual mode, and during the transition between one mode and the other, it is possible to configure a signal attenuation function ("bumpless transfer"). This feature avoids voltage/current dangerous surges and water hammers improving instrumentation longevity and reducing the associated maintenance costs.
Power Transducers - Max 18 V, 25 mA
Max Consumption - 1,5 W
Insulation - 1.500 Vac
Noise rejection - 50..60 Hz
Communication interface - RS485, ModBUS RTU, max 32 nodes (optional board)
Memory - Data memory, 10 years EEPROM
Operating temperature - -10..+60°C
Case - PPO self-extinguish DIN 43700
Front protecion degree - IP65
Terminals - Removable, pitch 3,5 – 5,08 mm
Dimension WxHxD - 98,5x44,5x90,5 mm
Cut-out dimension - 92x45 mm
Weight - 200 g
Settings - Front keys, password protect access
Anti-bump filter - From 0 to 255 s
Calibration - Yes, factory setting
Manual Mode - Setpoint value visualization with output retransmission
Automatic Mode - Measured value visualization with output scaling and retransmission
Special functions - Manual / Automatic mode, signal generator, anti-bump filter
Norms - EN 61000-6-4, EN 61000-6-2, EN 61010