●The electric heating cable adopts a low-temperature self-limiting electric heating cable. The maximum temperature of the eyewash tube does not exceed 38 degrees, which can effectively ensure that the internal water temperature of the eyewash tube will not be too high due to the continuous heating of the electric heating cable and the eye nerves of the injured person will be scalded.
●The temperature control system adopts a thermal resistance temperature controller. The factory set temperature is 35 degrees. When the temperature of the eyewash pipe is higher than 35 degrees, the electric heating cable will automatically power off and stop heating. The dual temperature control system is formed with the self-limiting temperature heating cable to ensure the safety of the equipment.
●Explosion-proof distribution box is equipped with power indicator and working indicator, which can observe whether the equipment is in normal working status in real time.
Height: 2410mm
Certificate & Standard: ANSI Z 358.1-2014, EN15154.1/2:2006
Pipe Wall Thickness: 2.5mm
Function: eye washing, body showering, water heating.
Working environment temperature: -25 ° C to 35 ° C
Inlet size: NPT 1 1/4″
Drain size: NPT 1 1/4″
Voltage:220V/50Hz(customizable)
Power: 200Watt(customizable)
Explosion proof level: Ex II T4-T6
Designed for cold weather, heat tracing cable will automatically turn on once the water temperature below setting parameter to make sure the water free from freeze.
By optional, it can equipped with an audible and visual alarm, once the user starts the eyewash or shower,alarm will start work simultaneously.