Input:
Voltage range: (three phase) 304V-456V, (single phase) 176V-264V
Frequency: 47Hz-63Hz
Output:
Rated voltage: (phase voltage)220V,(lin voltage)380V
(other voltage can be set as well, such as 400V and so son)
Regulation accuracy: ±(1-5)% tolerance(2% default)
Reponse time: qucik(one power frequency is 20ms)
Waveform distortion: No additional waveform disortion(static)
Efficiency: ≥98%
Three-phase voltage: three-phase voltage auto balance
Output delay: output after voltage stabilize
Protection:
Over voltage: output interrupt or bypass uninterruptedly when voltage over 10% (245V)
Under voltage: output interrupt or bypass uninterruptedly when voltage under 10% (195V)
Phase lack: with automatic cutout
Over load: electronic detection,output interrupted after overload 3mins
Over current: double protection by electronic detection and circuit breaker
Short circuit: double protection by electronic detection and circuit breaker
Bypass: bypass automatically and uninterruotedly
Indicator:
Voltage: three-phase respectively with the ture effective value of the LCD display
Current: three-phase respectively with the ture effective value of the LCD display
Working status: stabilized voltage/mains states
Unusual status: over voltage.under voltage.overlaod. blowout
Interface:
intelligent human-machine operation panel,
conveniently checking the various parameters
Working status:
with stabilized voltage and mains two ways of working
Overload capacity:
5 times rate current in 1 seconds
Interface:
intelligent human-machine operation panel,
conveniently checking the various parameters