600Volt. Aluminum AlloyConductorCross-Linked Polyethylene (XLPE) InsulationMoisture,Low-Temp, Oil, Gas, Sunlight ResistantSingle Conductor Underground Service Entrance Cable
APPLICATIONS
USEcable with single 8000 Series or 1350-H19 Aluminum Alloy conductoris suitable for use in conduit and raceways installed underground in conduit as specified in the USA National Electrical Code (NEC), at dry locations while conductor temperatures shall not exceed 90˚Cor wetlocationsat conductor temperatures shall not exceed 75˚C. USE is permitted for 600 volt applications.With the special insulation, the cable requires no lubrication for installation.USEis to be assembled with or without a bare (metal-coated) or insulated grounded conductor and without any overall covering other than an open, skeleton tape or wrap that.
600Volt. Aluminum AlloyConductorCross-Linked Polyethylene (XLPE) InsulationMoisture,Low-Temp, Oil, Gas, Sunlight ResistantSingle Conductor Underground Service Entrance Cable
STANDARDS
Morn’s USEAL complies with the following:
•ASTM B800, B801, B836, B230, B230M-07
•UL854
•USA National Electrical Code/NFPA 70, 2014Edition
CONSTRUCTION
Conductor
•Stranded compressed/compactedAA-8000 series or 1350-H19 aluminum alloy
Insulation
•As phase conductor: cross-linked polyethylene (XLPE) insulation, abrasion, moisture, heat, low-temp, oil, gas, sunlight Resistant
•As neutral conductor: cross-linked polyethylene (XLPE) insulation with yellow triple extrusion strips, abrasion, moisture, heat, low-temp, oil, gas, sunlight resistant