600 Volt.Copper Conductor, Cross-Linked Polyethylene (XLPE) Insulation, Moisture, Heat, Low-Temp, Oil, Gas, Sunlight Resistant Single Conductor Underground Service Entrance Cable
APPLICATIONS
USEcable is suitable for use in conduit and raceways installed underground in conduit as specified in the USA National Electrical Code (NEC), at dry locations while conductor temperatures shall not exceed 90˚Cor wetlocationsat conductor temperatures shall not exceed 75˚C. USE is permitted for 600 volt applications.
STANDARDS
Morn’sUSEcomplies with the following:
•ASTMB3,B8,B787
•UL 854
CONSTRUCTION
Conductor
•Solid soft-annealed uncoated copper (14-8 AWG)
•Stranded compressed/compacted soft-annealed uncoated copper (6 AWG-2000 kcmil)
Insulation
•As phase conductor: cross-linked polyethylene (XLPE) insulation, abrasion, moisture, heat, low-temp, oil, gas, sunlight Resistant
•As neutral conductor: cross-linked polyethylene (XLPE) insulation with yellow triple extrusion strips, abrasion, moisture, heat, low-temp, oil, gas, sunlight resistant