For use in heating, ventilating, air conditioning systems and district heating as a control valve in closed circuits
Technical Specifications
Stroke
20 mm
Leakage rate
Class IV (0…0.01% of volumetric flow)
Volumetric flow Vmin
5.7 m³/h
Valve characteristic
Linear
Rangeability
1:100
Material, valve body
Nodular cast iron GJS-400-18RT
Mounting position
Upright to 90° inclined
ΔPmin
55 kPa
SAX..P Δpmax
600 kPa
SAX..P Δps
700 kPa
SQV..P Δpmax
600 kPa
SQV..P Δps
700 kPa