Application of the wireless fire detection system is where only restricted use of cable or conduit is permitted because of structural or aesthetic reasons, or for reasons of architectural conservation.
By wireless coupling the complex or visible cable installation is void; this is particularly interesting for museums, churches, etc.
The system offers the additional advantage that installation is possible without interruption of operation.
With change or extension of the building, smoke detectors and manual call points can be displaced easily, without high investment. Bi-directional data communication in the frequency range of 868 - 870 MHz and 433 - 435 MHz.
The 3.6 V lithium battery (must be ordered separately) leads to a service life not less than 6 years.
Also available in different colors.
Technical Specifications
Standard
EN 54-17 , EN 54-18 , EN 54-25 , EN 300220-2
Radio frequency
868...870 MHz (SRD band) and 433...435 MHz
Channel width
50 kHz
Transmission distance
Max. 180 m in building Max. 1000 m in open air
Transmitting power
Typ. <10 (max. 25) mW ERP
Operating temperature
-10…55 °C
Supply voltage
Via FDnet or C-NET, additionally 3.6 V lithium battery, monitored
Transmitter/receiver antenna
Dual band antenna
Protection category
IP40; IP65 with housing
Relative humidity
≤95 % rel.
Color
Pure white, ~RAL 9010
Communication protocol
FDnet/C-NET
Dimensions (W x H x D)
89 x 167 x 28 mm
Number of addresses
2