6 safe digital inputs (+24 V DC/3 mA/0.5 ms)
2 safe digital outputs (+24 V DC/2 A)
Doubled clock output signal (short circuit proof)
SIL 3/PL e, Cat. 4
So that inputs can be tested and crossed circuits can be detected, 2 non-safe signal outputs, TA and TB, are provided. To use the SDM 081 in an application, a Safety CPU module is required.
For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet
Digital Inputs
Type -
standard
Number -
6
Input voltage -
+24 V DC (+18-30 V DC)
Input current -
3 mA at +24 V DC
Input delay -
0.5 ms
Cross-circuit detection signal outputs -
Yes
Digital Outputs
Type -
standard
Number -
2
Short-circuit proof, current limited -
Yes
Max. total current -
4 A
Voltage range -
+18-55 V DC
Output voltage -
+24 V DC
Max. Output current -
2 A
Mechanical Features
Dimensions -
12.5 x 104 x 72 mm (W x H x D)
Protection type -
IP20
Article Number/Certification
Article number -
20-895-081
Standardization/certification -
UL 508 (E247993)
SIL 3 according to EN 62061
PL e, Cat. 4 according to EN ISO 13849-1/-2