As a result of extending the range of functional applications of the MultiCon product line, the CMC-N16 wall mounted model has been designed. The new IP 65 enclosure allows using the device in harsh environments, where safe installation of a typical controller / data recorder in a panel mounted enclosure is impossible. Although the number of available inputs is reduced if compared with the panel mounted model, the functionality available so far has been maintained. Thanks to that it is one of the first industrial devices which integrates advanced control functions (PID, ON/OFF, time & profiles etc.) and logging of setpoints, excitations and current state of controlled objects. Based on Linux firmware, is stable and the touch screen makes configuration easy and comfortable and data presentation also readable and attractive. Although the Multicon CMC-N16 is build in a quite small housing, it can integrate up to 4 inputs, and its construction allows user almost free configuration by choosing from 13 available input/output blocks.
Input type -
4 universal inputs max.
2 universal pulse counter / ratemeter
5 digital inputs 24V DC
Input range -
0/4...20 mA
0/1...5V, 0/2...10V
0...30V
-10...25 mV, -10...100 mV, 0…600 mV, ±25 mV, ±100 mV
Pt100, Pt500, Pt1000 (PN-EN): -100...600°C, Pt'50, Pt'100, Pt'500 (GOST): -200...600°C, Ni100, Ni500, Ni1000 (PN-EN): -60...180°C, Cu50, Cu100: -50...200°C, Cu'50, Cu'100 (GOST): -200...200°C
TC K: -200...+1370°C, S: -50...+1768°C, J: -210...+1200°C, T: -200...+400°C, N: -200...+1300°C, R: -50...+1768°C, B: +250...+1820°C, E: -200...+1000°C
0...300Ω, 0...3kΩ