• Ex zone 1 and 21
• Thermoplastic enclosure
• Double insulated X
• With pre-wired cable
• Shaft bore ø 9.5 mm
• Actuating shaft can be turned 360°
• Attention: Please state required international approvals with your order!
Applied standards
EN 60947-5-1, EN ISO 14119, GS-ET-15, EN IEC 60079-0, EN 60079-1, EN 60079-31, EN ISO 13849-1
Enclosure
thermoplastic, glass-fibre reinforced, impact resistant, self-extinguishing UL 94 V-0
Switch type
type 1
Coding level
no coding
Degree of protection
IP65 (IEC/EN 60529)
B10d (10 % load)
2 million
TM
max. 20 years
Contact material
silver
Switching system
slow action, positive break NC contacts A
Switching elements
1 NC/1 NO contact, type Zb
Connection
pre-wired cable H05VV-F
Cable cross-section
4 x 0.75 mm² (incl. conductor ferrules)
Rated impulse withstand voltage Uimp
4 kV
Conventional thermal current Ithe
T6: 6 A, T5: 3 A
Utilisation category
AC-15; DC-13
Short-circuit protection
6 A gG/gN fuse
Ambient temperature
T6: –20 °C … +65 °C,
T5: –20 °C … +75 °C, +90 °C with max. 3 A
Mechanical life
> 1 million operations
Impact energy
max. 7 J
Ex marking
L II 2G Ex db IIC T6/T5 Gb,
L II 2D Ex tb IIIC T80 °C/T95 °C Db
IECEx Ex db IIC T6/T5 Gb,
Ex tb IIIC T80 °C/T95 °C Db
Approvals
PTB 03 ATEX 1068 X
IECEx PTB 06.0053X