Ceiling-mounted multi-sensor for detection of light and motion in rooms and office spaces. Energy-efficiency can be optimized through connecting the MDS to an automated constant light control and temperature reduction in unoccupied rooms. The flat design makes up for an inconspicuous installation in e.g. suspended ceilings. For mounting on concrete ceilings, a surface-mounted frame is available.
• Application/type : Ceiling sensor, Room sensor
• Purpose : Measure values
• Measured values : temperature, luminosity, motion
• Interface : Active, 0..10 V, Switch contact
• Configuration : potentiometer
• Sensor : PIR (passive infrared)
• Output voltage : 0..10 V, 2x 0..10 V, min. load 10 kΩ
• Output switch contact : 1x contact NO, load max. 1 A, for 24 V =/~, floating, with follow-up time 1 second..30 minutes, selectable at the device
• Operating range temperature (°C) : 0..+50
• Output signal temperature : 0..+50 °C
• Operating range humidity : max. 85% rH non-condensing
• Accuracy temperature : ±0,5 K (typ. at 21 °C)
• Measuring range light : 0..1000 lux (10 bit)
• Accuracy light : ±50 Lux
• Dectection range : cone-shaped, detection range, angle 105°, 444 detection zones – with an installation height of 2,7 m circular detection range will have a Ø=7 m
• Power supply : 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
• Power consumption : typ. 1,5 W (24 V =), 4 VA (24 V ~)
• Enclosure : ABS
• Colour : pure white
• Protection (IP) : IP20, according to EN 60529
• Connection : terminal block, max. 1,5 mm², pluggable
• Mounting : ceiling flush mount or with enclosure for surface mounting
• Packaging length (mm) : 120
• Packaging width (mm) : 100
• Packaging height (mm) : 100