Differential pressure transmitter DPA+ active
relativemembrane4-20 mA

Differential pressure transmitter - DPA+ active - Thermokon Sensortechnik - relative / membrane / 4-20 mA
Differential pressure transmitter - DPA+ active - Thermokon Sensortechnik - relative / membrane / 4-20 mA
Add to favorites
Compare this product

Characteristics

Pressure type
relative, differential
Technology
membrane
Output
4-20 mA, 0-10 V, 0-5 V
Electrical connection
terminal block
Supply voltage
24 Vdc, 32VDC, 15VDC
Mounting
surface-mount
Fluid
for air
Material
PVC
Protection level
IP65
Applications
process, for clean rooms
Other characteristics
with LCD display, MEMS
Pressure range

Min.: 0 Pa
(0 psi)

Max.: 7,000 Pa
(1.02 psi)

Process temperature

Min.: -10 °C
(14 °F)

Max.: 50 °C
(122 °F)

Description

Differential pressure transmitter for measuring and monitoring overpressure, underpressure, differential pressure and flow volume of air and other non-aggressive gases in fan and filter systems in duct applications. 8 adjustable pressure and flow volume ranges permit use in HVAC applications of clean rooms, process measurement and controls systems. The optional features, such as relay outputs for 2-point controllers or 2-stage 2-point controllers, an LCD with traffic light indication allow for a wide range of applications. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation. 'Dual' versions with 2 independent sensors for up to 2x differential pressures or 2x flow volume in a single enclosure are available. The mounting base (included in the delivery content) can be used to mount the DPA+ on a flat surface or on DIN rail TS35 (35x7,5 mm) in accordance with EN 60715. • Application/type : Differential pressure transducer • Purpose : Measure values • Measured values : differential pressure, volume flow, pressure in Pa or inchWC, volume flow in m³/h or cfm, optionally configurable via app or uConfig • Interface : Active, 0..5 V, 0..10 V, 4..20 mA, Switch contact • Configuration : USEapp, uConfig, jumper, DIP switches • Sensor : MEMS membrane measuring element • Output voltage : 2x 0..10 V or 0..5 V, 4x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ • Output current : 2x 4..20 mA, max. load 500 Ω • Output switch contact : 2x floating contact NO for 24 V ~ or 24 V = / 3 A • Operating range humidity : max. 85% rH short term condensation