Differential pressure transmitter for measuring and monitoring overpressure, underpressure, differential pressure and flow volume of air and other non-aggressive gases in fan and filter systems in duct applications. 8 adjustable pressure and flow volume ranges permit use in HVAC applications of clean rooms, process measurement and controls systems. In addition to LoRaWAN®, additional analog voltage outputs are available as interfaces. In radio-shielded mounting locations, an optional external antenna can be used to optimize the radio link between the device and the gateway. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation. 'Dual' versions with 2 independent sensors for up to 2x differential pressures or 2x flow volume in a single enclosure are available. The mounting base (included in the delivery content) can be used to mount the DPA+ on a flat surface or on DIN rail TS35 (35x7,5 mm) in accordance with EN 60715.
• Application/type : Differential pressure transducer
• Purpose : Measure values
• Measured values : differential pressure, volume flow, pressure in Pa or inchWC, volume flow in m³/h or cfm, optionally configurable via app or uConfig
• Interface : LoRaWAN® (868 MHz), Active, 0..5 V, 0..10 V
• Configuration : USEapp, DIP switches, LoRaWAN® Downlink
• Sensor : MEMS membrane measuring element
• Output voltage : 2x 0..10 V or 0..5 V, live-zero configuration via app or uConfig, min. load 10 kΩ
• Radio technology : LoRaWAN® (868 MHz)
• Data transmission : bidirectional