Cable sensor for temperature measurement in HVAC applications. Depending on the application requirements, different PVC, silicone and PTFE cables are available. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation. The TF14 with its 4 mm diameter pocket is well suited for fast response applications.
• Application/type : Cable sensor
• Purpose : Measure values
• Measured values : temperature
• Interface : Active, 0..5 V, 0..10 V, 4..20 mA
• Configuration : jumper
• Sensor : SI-Protection against permeation of humidity and mechanical stress (e.g. vibration)
• Output voltage : 0..10 V or 0..5 V, adjustable via jumper, min. load 5 kΩ
• Output current : 4..20 mA, max. load 500 Ω
• Operating range temperature (°C) : -50..+250
• Operating ranges temperature (°C) : -50..+180, -50..+250
• Output signal temperature : scaling analogue output, 0..+160 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer
• Operating range humidity : max. 85% rH short term condensation
• Accuracy temperature : ±0,5 K (typ. at 21 °C), within default measuring range, potentiometer for offset adjustment
• Power supply : 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
• Power consumption : typ. 0,4 W (24 V =), max. 0,5 W (24 V =), 0,8 VA (24 V ~)
• Material in touch with media : Sensor probe, Ø=4 mm, stainless steel V4A (1.4571), 16-point pressed (IP65), rolled (IP67)
• Installation length (mm) : 50, 100, 150
• Enclosure : USE-S, impact- and shock-resistant enclosure with quick-release cover, PC
• Colour : pure white