Contact sensor for temperature measurement (cold or hot water) on pipes and other curved surfaces. Spring-loaded brass contact sensor for a fast response. Models with a relay output for a 2-point controller or a 2-stage 2-point controller and color-changing LCD allow for a wide range of applications. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation.
• Application/type : Contact sensor
• Purpose : Measure values
• Measured values : temperature
• Interface : Passive
• Sensor : SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), Pt1000 DIN cl. B, Pt100 DIN cl. B, Pt1000 1/3 DIN, Pt100 1/3 DIN, Ni1000 DIN cl. B, Ni1000TK5000, NTC10k, NTC10k Precon, NTC10k Carel, NTC20k, NTC1,8k, NTC5k, LM235Z, KTY81-110, KTY81-121, KTY81-122, KTY81-210, DS18B20 1-wire, FeT/Staefa, passive
• Operating range temperature (°C) : -35..+120
• Operating ranges temperature (°C) : -35..+120
• Operating range humidity : max. 85% rH short term condensation
• Accuracy temperature : ±0,5 K (typ. at 21 °C), ±0,1 K (typ. at 0 °C), ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C), ±0,2 K (typ. at 25 °C, temperature dependend), ±0,3 K (typ. at 25 °C, temperature dependend), typ. ±0,3 K (typ. at 21 °C)